(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
Instead, please kindly use other browsers like Google Chrome, Microsoft Edge or Mozilla Firefox.

  • Scheduled Maintenance Notice: This site will be unavailable due to scheduled maintenance from 9:00 30/6/2024 to 6:00 (SGT) 1/7/2024. We apologize for the inconvenience.
  • Please Note our New Address (effective April 1, 2024): 331 North Bridge Rd, #05-01 Odeon 331, Singapore 188720.

SPD Class II for distribution boards (LT-332S)

SPD Class II for distribution boards LT-332S

SPD for power distribution board with built-in automatic disconnection device.
[Features]
・ JIS agreement type circuit breaker for wiring with 2-pole dimension width of 50 mm, easy to install in the panel
・ Built-in automatic disconnection device, SPD function display, deteriorated contact output compatible (S Type only), and a safety function even when it deteriorates
・ Excellent responsiveness, no follow current
・ With electric shock prevention terminal cover
・ 3 patterns for mounting (DIN rail / connecting mounting plate / screw mount with mounting bracket)
[Applications]
・ Protects various low voltage power supply circuits from lightning surges

PDF

Japanese Only

Part Number

Configured Part Number is shown.

LT-332S

 
Part Number
LT-332S
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Voltage when starting operations With degraded contact output terminal

SGD 223.37

1 Piece(s) 4 Day(s) or more -100V / 200VAC130/250VLine 1300 V or less/Ground 1500 V or lessLine 480V ± 10%Available

Loading...

  1. 1

Basic Information

Application Power Supply Type Integrated Mounting Method Crimp terminal attached
Class, category Class II Dimension vertical(mm) 107 Dimension width(mm) 50
Dimension depth(mm) 65 Nominal Discharge Current (8/20 μs) 10kA Maximum Discharge Current (8/20 μs) 20kA

Please check the type/dimensions/specifications of the part LT-332S in the SPD Class II for distribution boards series.

Similar Part Numbers

Part Number
LT-332
LT-334
LT-334S
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Voltage when starting operations With degraded contact output terminal

SGD 188.23

1 Piece(s) 4 Day(s) or more -200V / 100VAC130/250VLine 1300 V or less/Ground 1500 V or lessLine 480V ± 10%None

SGD 393.13

1 Piece(s) 4 Day(s) or more -400VAC510V2400V or lessLine 860 V ± 10%None

SGD 617.40

1 Piece(s) 10 Day(s) or more 10400VAC510V2400V or lessLine 860 V ± 10%Available

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)