Reverse Rotation Stop Relay APR-S

Caution
Product Description
Reverse rotation prevention relay APR-S
[Features]
· Voltage detection method three-phase motor reverse rotation prevention relay.
· Relay that prevents reverse rotation resulting from erroneous wiring.
· When powered on, it distinguishes between positive-phase, reverse, and reverse-phase.
· Magnet contact is prevented.
· With the wire connection method, open phase input is also prevented.
· Small plug-in type, with no adjustment needed.
· Because of the voltage detection method, it can be used irrespective of the load current.
Reverse Protection Relay APR-S Specifications

Reverse Protection Relay APR-S external appearance

APR-S outline drawing

APR-S dimensional outline drawing, Units: mm

APR-S terminal layout drawing
(Drawing viewed from back of main body)

APR-S380, APR-S440 outline drawing

APR-S380, APR-S440 dimensional outline drawing, Units: mm

APR-S380, APR-S440 terminal layout drawing
(Drawing viewed from back of main body)

APR-S external connection example
Operation description
When power lines R → S → T are energized to apply current in sequence to terminals (6) → (4) → (3) there is a positive phase sequence.
Positive phase sequence: built-in relay operation ((5)-(1) carrying current, (5)-(8) not carrying current).
Negative phase sequence: no built-in relay operation ((5)-(1) not carrying current, (5)-(8) carrying current).

APR-S380/S440 external connection example
- *For applied voltages and control voltages to contacts use a separate power supply.
Operation description
When power lines R → S → T are energized to apply current in sequence to terminals (10) → (1) → (3) there is a positive phase sequence.
Positive phase sequence: built-in relay operation ((6)-(7) carrying current, (6)-(8) not carrying current).
Negative phase sequence: no built-in relay operation ((6)-(7) not carrying current, (6)-(8) carrying current).

APR-S dimensions with sockets mounted, Units: mm
Model PF083A (sold separately)
| Rated Voltage | Model APR-S | 200/220 V |
|---|---|---|
| Model APR-S380 | 380/400 V | |
| Model APR-S440 | 440 V | |
| Allowable Voltage Fluctuation Range | Model APR-S | Three-phase 170 to 240 V AC 50/60 Hz |
| Model APR-S380 | Three-phase 350 to 420 V AC 50/60 Hz | |
| Model APR-S440 | Three-phase 410 to 460 V AC 50/60 Hz | |
| Operating Time | Within 100 ms (After voltage applied, until positive phase → reverse phase detected) | |
| Control Output | Model APR-S | 1 c relay output 200 V AC 1.1 A cosφ = 1, 200 V AC 0.6 A cosφ = 0.4 |
| Model APR-S380 | 1 c relay output 250 V AC 1.1 A cosφ = 1, 250 V AC 0.6 A cosφ = 0.4 | |
| Model APR-S440 | ||
| Ambient Operating Temperature | -10 to +50°C (assuming no icing) | |
| Lifespan | Mechanical | 1,000,000 operations min. |
| Electrical | 100,000 operations min. | |
| Weight | Approx. 100 g | |
- *See the catalog for specifications other than those detailed above.