GOT1000 External Input/Output Unit

Brand :
MITSUBISHI
Caution
Product Description
Mitsubishi GOT1000 External Input/Output Unit.
[Features]
·For the GOT1000 series.
[Applications]
·Used as an external input/output unit.
GOT1000 External Input/Output Unit Specifications

Product image of GOT1000 External Input/Output Unit
Specifications
(Unit: mm)

GT15-DIO dimensional drawing
GT15-DIO Specifications
| Category | Optional unit | ||
|---|---|---|---|
| Series | GOT1000 | ||
| Unit | External input/output unit | ||
| Product Type Name | GT15-DIO | ||
| Applicable Standards | UL/cUL, CE(EMC), KC, ABS, BV, DNV GL, LR, NK, RINA | ||
| Supported Models | GT27, GT25 (5.7 type, wide model, enhanced environmental resistance model, Handy GOT are excluded), GT16, GT15 | ||
| Common Specifications | External Connection Method | 50-pin connector | |
| Compatible Wire Size | AWG#28 or less | ||
| Operation Display | N/A | ||
| External Power Supply | Voltage | 24 V DC (+20%/-15%, ripple ratio within 5%) | |
| Current | 1.85 A | ||
| Dielectric Strength | 350 V AC for 1 minute | ||
| Internal Current Consumption | 0.10 A | ||
| Weight | 0.13 kg | ||
| Input Specifications (Source Type) | Input Method | Dynamic scan method | |
|---|---|---|---|
| Number of Inputs | 16 points / 128 points (16 × 8) (Output 8 points for scan) | ||
| Insulation Method | Opto-isolator insulation | ||
| Rated Input Voltage | 24 V DC (+20%/-15%, ripple ratio within 5%) | ||
| Rated Input Current | Approx. 4 mA | ||
| Input Derating | (External input/output unit [Positive common input / Sink type output] [for GOT2000 Series/GOT1000 Series] Refer to Instruction Manual.) | ||
| ON Voltage / ON Current | 15 V DC or more / 2 mA or more | ||
| OFF Voltage / OFF Current | 4 V DC or less / 1 mA or less | ||
| Input Resistance | Approx. 5.6 KΩ | ||
| Response Time | ON → OFF | 0.4 ms or less (24 V DC) | |
| OFF → ON | 0.4 ms or less (24 V DC) | ||
| Common Method | 16 points 1 common (common terminal: 0 V (Pin number 26 to 29)) | ||
| Dynamic Scan Cycle | 13.3 ms | ||
| Output Specifications (Sink Type) | Output Method | Direct output | |
| Number of Outputs | 16 points + 1 point (RUN output) | ||
| Insulation Method | Opto-isolator insulation | ||
| Rated Load Voltage | 24 V DC (+20%/-15%) | ||
| Max Load Current | 0.1 A / 1 point | ||
| Maximum Inrush Current | 0.7 A 10 ms or less | ||
| Leakage Current When OFF | 0.1 mA or less | ||
| Maximum Voltage Drop When ON | 0.2 V DC (Max.) 0.1 A | ||
| Protection Function | Available (Overload protection function, overheat protection function) | ||
| Response Time | ON → OFF | 1 ms or less (resistant load) | |
| OFF → ON | 1 ms or less | ||
| Common Method | 16 points 1 common (common terminal: 24 V (Pin number 1 to 4)) | ||
| Surge Suppressor | Zener diode | ||
Restrictions
- External power supply voltage: When the external power supply is cut off, a system alarm is generated.
- ON voltage / ON current, OFF voltage / OFF current: EN61131-2:2003 (digital input type 1) compatible
- Response Time: Time consumed in I/O part.
- Number of Outputs Points: RUN output ON: During normal operation / OFF: WDT error in GOT main body
- Protection function: A function to protect the internal elements of unit. It does not exist in RUN output. This is not a function to protect external devices. Automatically recovers when it is no longer overloaded or overheated. Overload protection function operates independently for each point with 1 to 3 A / 1 point. Overheat Protection Function operates independently for each point.
GT15-DIOR Specifications
| Category | Optional unit | ||
|---|---|---|---|
| Series | GOT1000 | ||
| Unit | External input/output unit | ||
| Product Type Name | GT15-DIOR | ||
| Applicable Standards | UL/cUL, CE(EMC), KC, ABS, BV, DNV GL, LR, NK, RINA | ||
| Supported Models | GT27, GT25 (5.7 type, wide model, enhanced environmental resistance model, Handy GOT are excluded), GT16, GT15 | ||
| Common Specifications | External Connection Method | 50-pin connector | |
| Compatible Wire Size | AWG#28 or less | ||
| Operation Display | N/A | ||
| External Power Supply | Voltage | 24 V DC (+20%/-15%, ripple ratio within 5%) | |
| Current | 1.85 A | ||
| Dielectric Strength | 350 V AC for 1 minute | ||
| Internal Current Consumption | 0.10 A | ||
| Weight | 0.13 kg | ||
| Input Specifications (Sink Type) | Input Method | Dynamic scan method | |
|---|---|---|---|
| Number of Inputs | 16 points / 128 points (16 × 8) (Output 8 points for scan) | ||
| Insulation Method | Opto-isolator insulation | ||
| Rated Input Voltage | 24 V DC (+20%/-15%, ripple ratio within 5%) | ||
| Rated Input Current | Approx. 4 mA | ||
| Input Derating | (External input/output unit [Negative common input / Source type output] [for GOT2000 Series/GOT1000 Series] refer to instruction manual.) | ||
| ON Voltage / ON Current | 15 V DC or more / 2 mA or more | ||
| OFF Voltage / OFF Current | 4 V DC or less / 1 mA or less | ||
| Input Resistance | Approx. 5.6 KΩ | ||
| Response Time | ON → OFF | 0.4 ms or less (24 V DC) | |
| OFF → ON | 0.4 ms or less (24 V DC) | ||
| Common Method | 16 points 1 common (common terminal: 0 V (Pin number 26 to 29)) | ||
| Dynamic Scan Cycle | 13.3 ms | ||
| Output Specifications (Source Type) | Output Method | Direct output | |
| Number of Outputs | 16 points + 1 point (RUN output) | ||
| Insulation Method | Opto-isolator insulation | ||
| Rated Load Voltage | 24 V DC (+20%/-15%) | ||
| Max Load Current | 0.1 A / 1 point | ||
| Maximum Inrush Current | 0.7 A 10 ms or less | ||
| Leakage Current When OFF | 0.1 mA or less | ||
| Maximum Voltage Drop When ON | 0.2 V DC (Max.) 0.1 A | ||
| Protection Function | Available (Overload protection function, overheat protection function) | ||
| Response Time | ON → OFF | 1 ms or less (resistant load) | |
| OFF → ON | 1 ms or less | ||
| Common Method | 16 points 1 common (common terminal: 24 V (Pin number 1 to 4)) | ||
| Surge Suppressor | Zener diode | ||
Restrictions
- External power supply voltage: When the external power supply is cut off, a system alarm is generated.
- ON voltage / ON current, OFF voltage / OFF current: EN61131-2:2003 (digital input type 1) compatible
- Response Time: Time consumed in I/O part.
- Number of Outputs Points: RUN output ON: During normal operation / OFF: WDT error in GOT main body
- Protection function: A function to protect the internal elements of unit. It does not exist in RUN output. This is not a function to protect external devices. Automatically recovers when it is no longer overloaded or overheated. Overload protection function operates independently for each point with 1 to 3 A / 1 point. Overheat Protection Function operates for each 2 points (with a combination of YD00/YD01 to YD0E/YD0F).