MELSEC-F Series CF Card Special Adapter

Brand :
MITSUBISHI
Caution
Product Description
Capable of storing up to 254 items of sequencer data of up to 32,767 lines in CSV format onto a CF card.
MELSEC-F CF Card Special Adapter Specifications

FX3U-CF-ADP image
- Capable of storing up to 254 items of sequencer data of up to 32,767 lines in CSV format onto a CF card.
- The stored CSV file can be read out with spreadsheet software, etc. and displayed for graph display and analysis.
- Stored data on the CF card can be read out to the sequencer line by line and used for sequence control.
Performance Specifications
| Data Sending/receiving Method | By application command of the basic unit | |
|---|---|---|
| Time Data | Operates with the time data of the basic unit | |
| DOS File System | FAT16 | |
| Maximum Data Capacity | 2 GB | |
| Maximum File Size | 512 MB (per file) | |
| Data Format | CSV format | |
| Maximum Number of Files | 63 files (when FIFO function is not used) | |
| FIFO Function File | 1 pattern. File name auto creation | |
| Data Saving Directory | Regular File | \FX3U_CF\DATA\.(Directory name fixed) |
| FIFO File | \FX3U_CF\DATA\FIFO\.(Directory name fixed) | |
| File Name Format | 8.3 format (extension is CSV fixed) Single-byte alphanumeric characters, symbols and character strings permitted by MS-DOS | |
| Number of Occupied Input/Outputs | 0 point (This has nothing to do with the maximum number of input/output points of the sequencer) | |
| Applicable Sequencer | For connecting to FX3U (Ver.2.61 or later), FX3UC (Ver.2.61 or later), FX3U and FX3UC-32MT-LT (-2), a function expansion board is required. Only one FX3U-CF-ADP can be added to the above sequencer, and it is handled in the same way as a communication function expansion board and communication special adapter, so it occupies one communication channel (ch). | |
| Weight | 0.3 kg (when CF card is not mounted) | |
| CF card ACCESS Switch Specifications | ||
| ON | Access permission to compact flash card | |
| OFF | No access to the compact flash card: When removing the compact flash card or turning off the FX3U-CF-ADP, make sure that the BUFFER LED and ACCESS LED are completely turned off after turning off the CF card ACCESS switch. | |
| Compact Flash Card Required Specifications | ||
| Operating Humidity | 5 to 95% RH (no condensation) | |
| Power Supply Voltage | 3.3 V (at 150 mA or lower) | |
| Connector Type | Type I | |
| Format Type | FAT16 (to have been formatted with FAT16) | |
| Data Capacity | 2 GB or less | |
| Connector Terminal | Gold plating | |
| Number of Boards That Can be Installed | 1 pc. | |
| Compatible Compact Flash Card | GT05-MEM-128 MC: Flash ROM 128 MB GT05-MEM-256 MC: Flash ROM 256 MB GT05-MEM-512 MC: Flash ROM 512 MB GT05-MEM-1 GC: Flash ROM 1 GB GT05-MEM-2 GC: Flash ROM 2 GB Compact flash card has a lifespan due to writing. In general, the lifespan of a compact flash card becomes short as the available space decreases. Make sure to keep enough free space. | |
| Power Supply Specifications | ||
| Adapter Drive Power Supply | Power Supply Voltage | 24 V DC +20%, -15%, ripple (p-p) within 5% |
| Allowable Momentary Power Outage Duration | Operation continues following a momentary power failure of 1 ms or less | |
| Current Consumption | Supply 24 V DC power to the 130 mA power connector. | |
| Interface Drive Power Supply | 5 V DC, 50 mA (internal power supply from 5 V DC power supply of sequencer) | |
General Specifications
| Ambient Temperature | 0 to 55°C: When operating, -25 to 75°C: When storing The ambient temperature upper limit must not exceed the compact flash card operating temperature limit of -20°C. For example: If the compact flash card operating temperature upper limit is 75°C, the ambient temperature upper limit is 55°C. | ||
|---|---|---|---|
| Relative Humidity | 5 to 95% RH (no condensation): when operating | ||
| Vibration Resistance | When Mounting to DIN Rail | Frequency: 10 to 57 Hz | Single Amplitude: 0.035 mm, 10 times in each direction of X, Y and Z (total of 80 minutes each) |
| Frequency: 57 to 150 Hz | Acceleration: 4.9 m/s2 10 times in each direction of X, Y and Z (total of 80 minutes each) | ||
| When Mounting Directly | Frequency: 10 to 57 Hz | Single Amplitude: 0.075 mm 10 times in each direction of X, Y and Z total of 80 minutes each) | |
| Frequency: 57 to 150 Hz | Acceleration: 9.8 m/s2 10 times in each direction of X, Y and Z (total of 80 minutes each) | ||
| Impact Resistance | 147 m/s2, for a duration of 11 ms, 3 times in each direction of X, Y and Z with a half-sine pulse | ||
| Noise Resistance | Achieved through a noise simulator with a noise voltage of 1,000 Vp-p, noise width of 1 μs, the rise time of 1 ns and frequency of 30 to 100 Hz | ||
| Dielectric Strength | Between all terminals and the earth terminal: 500 V AC for 1 minute | ||
| Insulation Resistance | Between all terminals and the earth terminal: 5 MΩ or more at 500 V DC on an ohmmeter | ||
| Grounding | D-type grounding (grounding resistance: 100 Ω or less)<Do not use common grounding with high-power systems> For grounding, please use a dedicated or shared grounding. | ||
| Operating Atmosphere | There shall be no corrosion gas or flammable gas and not much conductive dust | ||
| Altitude of Use | 2,000 m or lower Cannot be used in environments pressurized higher than the atmospheric pressure. Doing so may cause failure. | ||