CC-Link Space Optical Repeater

Brand :
MITSUBISHI
Caution
Product Description
Space optical repeater unit that extends the maximum CC-Link distance.
[Features]
· Optical repeater unit for general-purpose sequencers.
· Communication with a linear movement body.
[Applications]
· Network communication.
CC-Link Repeater Unit Space Optical Repeater Unit Specifications

AJ65BT-RPI-10A/AJ65BT-RPI-10B external appearance

AJ65BT-RPI-10A/AJ65BT-RPI-10B dimensional drawing (unit: mm)
| Product Name | Type Name | Contents | Number of Occupied Points | Station Type |
|---|---|---|---|---|
| Space optical repeater unit | AJ65BT-RPI-10A | AJ65BT-RPI-10A and AJ65BT-RPT-10B are used as a set Compatible with 156 k / 625 k / 2.5 Mbps, Spatial transmission from 0 to 100 m with infrared rays Optical communication status monitor function | -/1 | Remote I/O with one station occupied |
| AJ65BT-RPI-10B | -/1 | Remote I/O with one station occupied |
Common Items
| Optical Communication Specifications | - | |
|---|---|---|
| Optical Transmission Distance | 0 to 100 m | |
| Direction Angle | When the optical transmission distance is from 0 to 50 m: full angle of 2° When the optical transmission distance is from 50 to 100 m: full angle of 1° | |
| Modulation Frequency | A unit → B unit: 36 ±3 MHz B unit → A unit: 44 ±2.5 MHz | |
| Modulation Method | FSK | |
| CC-Link Specifications | - | |
| Transmission Speed | 156 kbps / 625 kbps/ 2.5 Mbps (selectable) | |
| Maximum Number of Segment Connection Stages | AJ65BT-RPI only: 2 stages Combination of AJ65BT-RPI and AJ65SBT-RPT: 3 stages Combination of AJ65BT-RPI, AJ65SBT-RPS, AJ65SBT-RPG, AJ65FBTA-RPH and AJ65BTS-RPH: 2 stages | |
| Maximum Transmission Distance of Each Segment | Varies depending on the transmission speed | |
| Maximum Number of Connected Devices | 64 devices | |
| Number of Occupied Stations | Monitor function used: 1 station Monitor function not used: 0 station | |
| Dielectric Strength | Between all DC external terminals and earth: 500 V AC for 1 minute | |
| Insulation Resistance | Between all DC external terminals and earth: 10 MΩ or more at 500 V DC on an ohmmeter | |
| Unit Power Supply | Voltage | 20.4 to 26.4 V DC |
| Current | 137 mA (when TYP. 24 V DC) | |
| External Dimensions | Height (H) | 100.0 mm |
| Width (W) | 161.0 mm | |
| Depth (D) | 57.5 mm | |
| Weight | 0.5 kg | |
| Operating Ambient Temperature | 0 to 50°C | ||
|---|---|---|---|
| Storage Ambient Temperature | -20 to 75°C | ||
| Operating Ambient Humidity | 10 to 90% RH, no condensation | ||
| Ambient Storage Humidity | 10 to 90% RH, no condensation | ||
| Vibration Resistance | JIS B 3502, IEC 61131-2 Compatible | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, single amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
| Under Continuous Vibration | Frequency: 5 to 8.4 Hz, single amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, constant acceleration: 4.9 m/s2 | ||
| Impact Resistance | JIS B 3502, IEC 61131-2 compatible (490 m/s2, 10 times in 3 directions of X, Y and Z) | ||
| Operating Atmosphere | There shall be no significant amount of dust and no corrosive gas | ||
| Ambient Illuminance | 10,000 lx or less (not subject to direct sunlight) | ||
| Cooling Method | Self-cooling | ||
| Operating Altitude | 0 to 2,000 m | ||
| Installation Location | Indoors | ||
| Overvoltage Category | II or less | ||
| Pollution Degree | 2 or less | ||