Heat Resistant Vinyl Cable, AWM1283/TEW (UL1283) Series

Caution
- The product image is a representative image. Specifications may vary by part number, including shape and color.
Product Description
A heat resistant vinyl cable with excellent flame retardancy compliant with UL/CSA standards.
[Features]
· To be used for internal wiring of electric/electronic equipment.
·Flexible stranded wire is used for the conductor, making it highly flexible and easy to work with
·Rated temperature: 105°C
[Applications]
· Suitable for various applications such as internal wiring of electrical and electronic equipment of 600 V or less and wiring inside panels.
|
Structure table of AWM1283/TEW (UL1283) Series

AWM1283/TEW (UL1283) Series
| Part number | AWG size | Color | Overall length m | *Calculated cross-sectional area mm2 | Conductor | Insulator thickness mm | Overall diameter Approx. mm | Maximum conductor resistance (20°C) Ω/km | Minimum insulation resistance (20°C) MΩ·km | Test voltage V/min. | Allowable current A | Standard Sales Length m | Approximate Weight kg/km | |
| Configuration Number of strands / Strand diameter mm | Outer diameter mm | |||||||||||||
| UL1283 | 8 | BE (Blue) R (Red) G (Green) GY (Green/Yellow, straight) W (White) BK (Black) | 10 / 50 / 100 / 153 (1 roll) | 8.37 | 7/24/0.26 TA | 4.4 | 1.65 | 7.7 | 2.20 | 50 | AC 3000 | 65 | 153 | 125 |
| 6 | 13.30 | 7/38/0.26 TA | 5.6 | 8.9 | 1.39 | 88 | 180 | |||||||
| 4 | 21.25 | 7/60/0.26 TA | 7.0 | 10.3 | 0.880 | 118 | 265 | |||||||
| 2 | 33.62 | 19/35/0.26 TA | 8.9 | 12.2 | 0.556 | 160 | 395 | |||||||
*UL1283 GY (green/yellow, straight) is a green wire core with a yellow band (approximately 30% retention).
*For the outer diameter of the cable and wire sheath (outer sheath), please refer to the "Overall Diameter" item in the table above.
Current Reduction Factor
| Ambient temperature (°C) | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Current Reduction Factor | 0.97 | 0.93 | 0.89 | 0.86 | 0.82 | 0.77 | 0.73 | 0.68 | 0.63 | 0.58 | 0.52 | 0.45 | 0.37 | 0.26 | 0 |
The allowable current value is a calculated value when 1 line is installed in the air at an ambient temperature of 30°C, and is not a guaranteed value.
If the ambient temperature is 30°C or higher, multiply the allowable current by the above current reduction factor.
(Example) Allowable current value for 24 AWG and ambient temperature of 40°C
5 x 0.93 = 4.65 (A)