Smart Positioner IP8001/8101 Series (Lever Type / Rotary Type)

Caution
- ■ For selection / technical information and characteristics on SMC air cylinder products,
check here.
■ Handling SMC products
Web pages for products currently without individual pages on this site will be released on an ad-hoc basis.
Click here for a quotation or to make an order if you have a model number. - Refer to the manufacturer's catalog for specification and material details.
- Product images may be representative images. Refer to the manufacturer's catalog for shape details.
Product Description
Equipped with a microcomputer and sensor, it allows for changing and monitoring various parameters easily from remote location.
[Features]
· Dust-proof / waterproof performance.
· Explosion-proof structure.
· Monitoring function.
· With internal opening indicator plate.
· With external scale plate (rotary type, back side mounting).
· Possible to set various parameters easily by using the built-in push buttons.
· Zero/Span adjustment is easier than conventional mechanical positioners.
· Output function has been enhanced.
· Control status is indicated.
· Supports 2-wire input of existing equipment.
· HART communication function
· Mounting compatibility.
· Energy saving.
Drawing
IP8001 (Lever type)
IP8000-0□0/0□3

□-IP8001-0□2/0□4-W

IP8101 (Rotary type)
IP8101-0□0/0□3-W

□-IP8101-0□2/0□4

Product Specifications
Product Specifications
| Items | Part number | |
|---|---|---|
| IP8001 | IP8101 | |
| Smart positioner | ||
| Lever type | Rotary type | |
| Single/double acting | ||
| Input current | 4 to 20 mA DC (standard)^*2) | |
| Minimum operating current | 3.85 mA DC or more | |
| Voltage between terminals | 12 V DC (Equivalent to input resistance of 600 Ω, at 20 mA DC) | |
| Maximum supply power | 1W (Imax: 100 mA DC, Vmax: 28 V DC) | |
| Supply air pressure | 0.14 to 0.7 MPa | 0.3 to 0.7 MPa |
| Standard stroke | 10 to 85 mm (Allowable runout angle 10 to 30°) | 60 to 100°^*3) |
| Sensitivity^*4) | Within 0.2% F.S. | |
| Linearity^*4) | Within ±1% F.S. | |
| Hysteresis^*4) | Within 0.5% F.S. | |
| Repeatability^*4) | Within ±0.5% FS | |
| Temperature coefficient | 0.05% F.S./°C or less | |
| Supply pressure fluctuation | -^*5) | |
| Output flow rate^*6) | 80 L/min (ANR) or higher (SUP = 0.14 MPa), 200 L/min (ANR) or higher (SUP = 0.4 MPa) | |
| Air consumption^*6) | 2 L/min (ANR) or less (SUP = 0.14 MPa) 4 L/min (ANR) or less (SUP = 0.4 MPa) | 11 L/min (ANR) or less (SUP = 0.4 MPa) |
| Ambient temperature and operating fluid temperature | General structure: -20 to 80°C | |
| ATEX intrinsically safe explosion-proof: -20 to 80°C (T4/T5) -20 to 60°C (T6) | ||
| Explosion-proof structure^*7) | ATEX intrinsically safe explosion-proof structure (II1G Ex ia IICT4/T5/T6 Ga) | |
| ATEX intrinsically safe explosion-proof Parameters (current circuit) | Ui ≤ 28 V, Ii ≤ 100 mA, Pi ≤ 0.7 W Ci ≤ 12.5 nF, Li ≤ 1.5 mH | |
| Outer cover protective structure | JISF8007 IP65 (compliant with IEC 60529) | |
| Communication method^*7) | HART communication | |
| Air connection port^*8) | Rc1/4 female thread, NPT1/4 female thread, G1/4 female thread | |
| Electrical wiring connection port^*8) | G1/2 female thread, M20 × 1.5 female thread, NPT1/2 female thread | |
| Material/painting | Main body: die-cast aluminum / modified epoxy-based baked coating | |
| Weight | Approx. 2.6 kg | |
*1) The specification values are at room temperature (20°C).
*2) Standard products are available for 1/2 split range. For use with 1/2 split range, please add 1% respectively to the linearity and hysteresis characteristics in the specification table.
*3) The stroke adjustment of 0 to 60° and 0 to 100° is possible.
*4) Accuracy-related characteristics vary depending on the combination with other equipment consisting the loop, such as positioners and actuators.
*5) Pressure fluctuation will not cause any changes in the output, however, if supply pressure setting is changed after the last calibration, please adjust the balance current and perform calibration again.
*6) Air is constantly consumed. Note that (ANR) refers to JIS B0120 standard air.
*7) For explosion-proof structure and HART communication, models must be specified.
*8) Screw types can be specified by selecting the model.
Product Specifications
| Items | Part number | ||
|---|---|---|---|
| IP8□01-0□2 (Non explosion-proof) | 52-IP8□01-0□4 | ||
| Smart positioner | |||
| Analog Output | Wiring method | 2-wire type | |
| Output signal | 4 to 20 mA DC | ||
| Power supply voltage | DC10 to 28 V | ||
| Load resistance | 0 to 750Ω | ||
| Accuracy | ±0.5% F.S. or less^*1) | ||
| Hysteresis | — | ||
| Alarm Output 1, 2 | Wiring method | 2-wire type | |
| Compatible standard | — | DIN19234/NAMUR Standard | |
| Power supply voltage | DC10 to 28 V | DC5 to 28 V | |
| Load current | 10 to 40 mA DC | (constant current output) | |
| Alarm ON | R = 350Ω±10% | ≥ 2.1 mA DC | |
| Alarm OFF (leak current) | 0.5 mA DC or less | ≤ 1.2 mA DC | |
| Response time | 50 msec or less | ||
*1) It indicates the analog output accuracy for the position values (P value) on the LCD display.