SPD for Device

SPD for Device

Click this image to zoom it.

Move the mouse over the image to zoom

  • Volume Discount

Built-in disconnection mechanism / degradation display included. JIS C 5381-1 Category II Compliant


· Built-in disconnection mechanism/With degradation display
· A built-in detachment mechanism for degrading ZnO element prevents SPD ignition/fuming
· Operational display function for the detachment mechanism
· Compact and space-saving
· Inter cable and ground integrated model for all-in-one protection against inductive lightning surges between cables and ground
· Uses multi-terminal elements to achieve the smallest size in the industry
· Lightning surge resistance capacity for peace of mind
· Offers maximum discharge current of 5 kA (8/20 μs) to withstand large lightning surges
· It can withstand 500 lightning surges of 1,000A and offers long life
· EN 61643-11 (2002 Stipulation) TÜV Approved (TÜV SÜD Japan)
· Uses UL Standard (UL 1449 3rd Edition)/CSA Standard (C22. 2 No. 8) approved flame-retardant material (UL V-0)

PDF

Part Number

Configured Part Number is shown.

Specifications

SPD for Device:Related Image

Model NumberWeight (g)Operating Temperature Range
MSPD-12C40-20 °C ~
+70 °C
MSPD-32C45

More Information

SPD for Device:Related Image
SPD for Device:Related Image
SPD for Device:Related Image
Characteristics Table
Model NumberApplicable VoltageMaximum Continuous Use VoltageDC Discharge Start Voltage (line-earth)DC Operation Starting Voltage (line-line)Nominal Discharge Current (8 / 20 µs)Voltage Protection Level (Up)Maximum Discharge Current (Imax) 8 / 20 µsSurge Current Life
MSPD-12C250 Vr.m.s.L-E,L-L:275Vr.m.s.800V ±20%540V ±10%2500A1.5kV5000A1000 A 500 Times
MSPD-32C250 Vr.m.s.L-E,L-L:275Vr.m.s.800V ±20%540V ±10%2500A1.5kV5000A1000 A 500 Times

SPD for Device:Related Image
Part Number
MSPD-12C
MSPD-32C
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSNumber of phases, number of wires

SGD 77.98

1 Piece(s)Available 4 Day(s) or more 101-phase 2-wire

SGD 78.03

1 Piece(s)Available 4 Day(s) or more 103-phase 3-wire

Loading...

  1. 1

Basic Information

Application For power supply Voltage AC100V Model Integrated type
Class, category Class II Representative standards UL / CUL / TUV / CSA Dimension vertical(mm) 33.5
Dimension width(mm) 38 Dimension depth(mm) 28 Maximum Continuous Operational Voltage 275 VAC
Nominal Discharge Current (8/20 μs) 2,500 A Maximum Discharge Current (8/20 μs) 5,000 A Voltage protection level 1.5 kV
Direct current discharge starting voltage To Ground 800V ± 20 % Voltage when starting operations Line-to-line 540V ± 10 %

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(65) 6733 7211 / FAX:(65) 6733 0211
9:00am - 6:00pm (Monday - Friday)