SPD for Telephone Line SG-TJ Series

SPD for Telephone Line SG-TJ Series

Compatible to categories C2 and D1 plug in type for telephone line

[Features]
Compatible to IEC categories C2 and D1.
· Impulse durability.
· C2: 8/ 20 μ s20kA, D1: 10 / 350 μ s10kA (C2: positive and negative, 5 times each, total 10 times, D1: positive and negative 1 time each, total 2 times).
· DIN rail compatible.
· Plug in type (easy to inspect and replace).
· Ideal for protecting solar generating systems

PDF

Japanese Only

Part Number

Configured Part Number is shown.

SG-T150J

 
Part Number
SG-T150J
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

SGD 224.39

1 Piece(s) 4 Day(s) or more

Loading...

  1. 1

Basic Information

Application Power line Type Single pole type Mounting Method Crimp terminal attached
Class, category IEC category C2 / IEC category D1 Dimension vertical(mm) 72.5 Dimension width(mm) 32.4
Dimension depth(mm) 69 Maximum Continuous Operational Voltage DC70.0V Impulse resistance (8/20 μs) 20kA
Impulse resistance (10/350 μs) 10kA Voltage protection level Line 400V/Ground 500V

Please check the type/dimensions/specifications of the part SG-T150J in the SPD for Telephone Line SG-TJ Series series.