SPD Class II for distribution boards

SPD Class II for distribution boards

SPD for power distribution board with built-in automatic disconnection device.
[Features]
・ JIS agreement type circuit breaker for wiring with 2-pole dimension width of 50 mm, easy to install in the panel
・ Built-in automatic disconnection device, SPD function display, deteriorated contact output compatible (S Type only), and a safety function even when it deteriorates
・ Excellent responsiveness, no follow current
・ With electric shock prevention terminal cover
・ 3 patterns for mounting (DIN rail / connecting mounting plate / screw mount with mounting bracket)
[Applications]
・ Protects various low voltage power supply circuits from lightning surges

PDF

Japanese Only

Part Number

Configured Part Number is shown.

 
Part Number
LT-332
LT-332S
LT-334
LT-334S
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipRoHSVoltage Maximum Continuous Operational Voltage Voltage protection level Voltage when starting operations With degraded contact output terminal

SGD 188.23

1 Piece(s) 4 Day(s) or more -100V / 200VAC130/250VLine 1300 V or less/Ground 1500 V or lessLine 480V ± 10%None

SGD 223.37

1 Piece(s) 4 Day(s) or more -100V / 200VAC130/250VLine 1300 V or less/Ground 1500 V or lessLine 480V ± 10%Available

SGD 393.13

1 Piece(s) 4 Day(s) or more -400VAC510V2400V or lessLine 860 V ± 10%None

SGD 617.40

1 Piece(s) 10 Day(s) or more 10400VAC510V2400V or lessLine 860 V ± 10%Available

Loading...

  1. 1

Basic Information

Application Power Supply Type Integrated Mounting Method Crimp terminal attached
Class, category Class II Dimension vertical(mm) 107 Dimension width(mm) 50
Dimension depth(mm) 65 Nominal Discharge Current (8/20 μs) 10kA Maximum Discharge Current (8/20 μs) 20kA